Data center UPS String 1 on bypass — battery fault

S24-2026-00476 · opened 06 Sep 2026, 10:22 AM · Hardware Failure

Priority

P1 · Critical

Status

Waiting Approval

SLA

Breached

Channel

onsite

APC Smart-UPS SRT 10kVA (DC-PWR-001) has transferred to internal bypass after reporting a battery string fault. No redundancy on this rack row until resolved.

Business impact

Loss of UPS protection for one data center rack row. A mains event would cause an immediate outage.

Affected users

1,800

Contact person

Nasir Uddin

Escalation level

L2

Engineer assessment

Both external battery packs are past service life and holding under 20% capacity. Unit is out of warranty. Recommend full battery pack replacement (2 units) plus a capacitor health check. Quotation submitted for approval.

Parts used

PartQtyUnit costTotal
APC SRT192BP Battery Pack2৳ 96,000৳ 1,92,000

Activity timeline

  1. Ticket created

    06 Sep 2026, 10:22 AM · Nasir Uddin

  2. Engineer on site

    06 Sep 2026, 12:05 PM · Md. Rahim Hasan

  3. Assessment completed, quotation raised

    06 Sep 2026, 01:40 PM · Md. Rahim Hasan

  4. Awaiting client approval on quotation Q-2026-0311

    06 Sep 2026, 01:45 PM · System

Comments

NU

Nasir Uddin · IT Manager · 07 Sep 2026, 01:10 AM

Reviewing the quotation with Finance this morning. Please stage the parts so we can act immediately on approval.

SLA

Response target06 Sep 2026, 10:52 AM
Responded06 Sep 2026, 10:40 AM
Resolution target06 Sep 2026, 02:22 PM
Current stateBreached

Affected asset

Data Center UPS String 1 — APC Smart-UPS SRT 10kVA

Head Office Data Center

Assigned engineer

Md. Rahim Hasan

Senior Infrastructure Engineer

Servicing24 Limited

+880 1711 204512

rahim.hasan@servicing24.com

Rating 4.8 / 5

Attachments

ups-battery-report.pdf180 KB